PEMP Generator Parts Store
Original ATS330AC ATS Controller Generator Dual Power Automatic Transfer Switch
Original ATS330AC ATS Controller Generator Dual Power Automatic Transfer Switch
No se pudo cargar la disponibilidad de retiro
Summary
The ATS330AC is a dual power automatic switching controller for mains and standby power switching applications, allowing automatic or manual control of ATS dual power switching. It has a dot matrix high resolution LCD display which shows power status, switch status, frequency, voltage, phase sequence and other parameters; the operating modes (manual, automatic, power failure) indicate the ATS switch operating status through LED indicators.
There are Chinese/English interface options, more language can be set according to user’s request. All parameters of the controller can be adjusted via the controller panel keys or by using a PC (external RS485 expansion module) to meet the different application requirements of the user.
Main Features
Dual core 32bit high performance single chip microcomputer.
AC power supply: Voltage operating range. (AC: 100-260V)
LCD screen, Available in Chinese/English languages, user’s language set if necessary.
The voltage and frequency of the mains and standby power supply can be displayed.
Automatic/Manual mode.
Suitable for various AC systems (3 phase 4-wires,, single-phase 2-wire, and 2-phase 3-wire).
Input/output function, status can be shown directly.
Totally 4 relays output.
Totally 1 configurable switch input.
A black box function, which saves the relevant parameters of the unit when a fault alarm occurs, making it easy to find the cause of the unit's failure.
Acquisition and display of parameters such as voltage, frequency, etc.
Control Protection: Realize automatic ATS switching of generator sets, perfect fault display and protection functions.
Standard water-proof rubber gasket. The waterproof can reach IP65.
Module design: All the connections are adapted with European connectors so that installation, connection, repair and replacement can be more easily.
Extensible RS485 interface: The connection of the extensible RS485 allows the use of the MODBUS protocol to achieve the "three remote" function.
Parameters
|
Options |
Parameters |
|
Working voltage |
AC 100V-260V(L1N1/L2N2) |
|
Power consumption |
Standby:MAX 1W |
|
Working:MAX 2W |
|
|
S1 Voltage Input |
3P4W 100VAC-260VAC (ph-N) |
|
S2 Voltage Input |
3P4W 100VAC-260VAC (ph-N) |
|
MAX Accumulating Time |
99999.9Hours (Min Store time:6min) |
|
Closing S1 output |
250VAC/16 AMP Non-contact normally Open output |
|
Closing S2 output |
250VAC/16 AMP Non-contact normally Open output |
|
Double split output |
250VAC/3 AMP Non-contact normally Open output |
|
Remote start S2 output |
30VDC/1 AMP Non-contact normally close output |
|
Fire input |
Fire input signal earth active |
|
Closing feedback input |
The Closing feedback signal is valid |
|
Working condition |
-25-65℃ |
|
Storage condition |
-40-85℃ |
|
Protection Level |
IP65:when waterproof rubber gasket is added between controller and its panel |
|
Insulation strength |
Apply AC 2.2kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3mA within 1min. |
|
Overall dimension |
106mm*86mm*45mm |
|
Panel cutout |
78mm*66mm |
|
Weight |
0.3Kg |